Authenticated PLC runtime crash via unchecked device name
Published Jul 18, 2026 · Updated Jul 18, 2026
Heap-based buffer overflow in OpenPLC Runtime b470206 and earlier allows remote authenticated users to crash the PLC runtime via /modbus. getData() copies an oversized device_name from mbconfig.cfg into the 100-byte MB_device.dev_name field without a length parameter or bounds check. Web-interface authentication is required; heap corruption overwrites adjacent configuration fields and interrupts the PLC process control loop.
Summary
What happened
Heap-based buffer overflow in OpenPLC Runtime b470206 and earlier allows remote authenticated users to crash the PLC runtime via /modbus. getData() copies an oversized device_name from mbconfig.cfg into the 100-byte MB_device.dev_name field without a length parameter or bounds check. Web-interface authentication is required; heap corruption overwrites adjacent configuration fields and interrupts the PLC process control loop.
The record
- CVE
- CVE-2026-11826
- Published
- Jul 18, 2026
- Updated
- Jul 18, 2026
- Vendor
- OpenPLC Project
- Product
- OpenPLC Runtime
- Classifications
- CWE-122, T0814
- Attack vector
- network
- Privileges
- authenticated
Timeline
How it unfolded
- Jul 18, 2026CVE publishedPublication date reported by the CVE source.
- Jul 18, 2026Record updatedLatest update available in the CVE record.
Exploitability
Present is not the same as exploitable
Compare your product and version with the public record. A matching version still requires validation against your environment.
Is a vulnerable build present?
Compare these published version ranges with your installed build and any vendor patches.
- Affected versionversion=0 <=b470206
What conditions does exploitation require?
What is affected?
Published CVSS scores
CVSS describes severity. EPSS estimates exploitation probability.
Attacks
What attackers are doing with it
Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.
Public exploit references
- OpenPLC getData heap-overflow proof of conceptproof of concept · demonstrated
Labels summarize the accepted research assessment. They do not indicate a test against your environment.