CVE-2024-8933Public exploitNetwork attack vector

Password-hash disclosure via cleartext UMAS project transfers

Published Nov 13, 2024 · Updated Nov 13, 2024

Cleartext credential exposure in Schneider Electric Modicon controllers allows attackers to capture project password hashes. UMAS project upload and download messages transfer the full APX binary without encryption, exposing its Base64-encoded password hash and salt. A passive position inside the logical network and a concurrent legitimate project transfer are required; the recovered values enable offline cracking or pass-the-hash access to a reserved controller session.

CVSS severity7.5
High
EPSS probability0.29%
Next 30 days · Sep 16, 2026
Known exploitationUnconfirmed
Based on sourced intelligence
Hinoki checkNot available
Coverage for this vulnerability

See if you're affected

Explore vulnerability checks for your environment with Hinoki.

Book a demo

Summary

What happened

Cleartext credential exposure in Schneider Electric Modicon controllers allows attackers to capture project password hashes. UMAS project upload and download messages transfer the full APX binary without encryption, exposing its Base64-encoded password hash and salt. A passive position inside the logical network and a concurrent legitimate project transfer are required; the recovered values enable offline cracking or pass-the-hash access to a reserved controller session.

The record

CVE
CVE-2024-8933
Published
Nov 13, 2024
Updated
Nov 13, 2024
Vendor
Distributed Data Systems
Product
Modicon Momentum Unity M1E Processor
Classifications
CWE-924, T0842
Attack vector
network
Privileges
unauthenticated

Timeline

How it unfolded

  1. Nov 13, 2024CVE publishedPublication date reported by the CVE source.
  2. Nov 13, 2024Record updatedLatest update available in the CVE record.

Exploitability

Present is not the same as exploitable

Compare your product and version with the public record. A matching version still requires validation against your environment.

Is a vulnerable build present?

Compare these published version ranges with your installed build and any vendor patches.

  1. Affected versionversion=0 <*
  2. Affected versionversion=All Versions

What conditions does exploitation require?

Attack vectornetwork
Required privilegesunauthenticated

What is affected?

Distributed Data Systems · Modicon Momentum Unity M1E Processorversion=0 <*; version=All Versions
Distributed Data Systems · Modicon M340 Processorsversion=0 <*
Distributed Data Systems · Modicon MC80version=0 <*; version=All versions
Distributed Data Systems · Modicon M340 CPUversion=All versions

Published CVSS scores

7.5Schneider ElectricCVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
7.5Schneider ElectricCVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H

CVSS describes severity. EPSS estimates exploitation probability.

Attacks

What attackers are doing with it

Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.

Daily unique IPsNo honeypot observations are available for this CVE in the selected window.

No observations available

Sep 10, 2026Sep 16, 2026
Latest reporting daySep 16, 2026
Latest daily unique IPsUnavailable
Prior 30-day averageUnavailable
SourceShadowserver honeypots (KEV)
Vectornetwork
Privilegesunauthenticated
Known exploitationUnconfirmed
Public exploitPublished

Weakness, pattern, technique

CWE-924Improper Enforcement of Message Integrity During Transmission in a Communication Channel
T0842Network Sniffing

Public exploit references