CVE-2024-5659

Unrecoverable controller fault via abnormal mDNS packet

Published Jun 14, 2024 · Updated Aug 1, 2024

Denial of service in Rockwell Automation controllers at firmware 34.011 or 4.001 allows attackers to trigger an unrecoverable fault. The mDNS listener mishandles an abnormal multicast packet sent to UDP port 5353; Rockwell has not disclosed the specific parsing or control-flow error. No authentication or user interaction is required, and one packet can fault every affected controller on the same network, interrupting control availability.

CVSS severity8.3
High
EPSS probability0.31%
Next 30 days · Sep 16, 2026
Known exploitationUnconfirmed
Based on sourced intelligence
Hinoki checkNot available
Coverage for this vulnerability

See if you're affected

Explore vulnerability checks for your environment with Hinoki.

Book a demo

Summary

What happened

Denial of service in Rockwell Automation controllers at firmware 34.011 or 4.001 allows attackers to trigger an unrecoverable fault. The mDNS listener mishandles an abnormal multicast packet sent to UDP port 5353; Rockwell has not disclosed the specific parsing or control-flow error. No authentication or user interaction is required, and one packet can fault every affected controller on the same network, interrupting control availability.

The record

CVE
CVE-2024-5659
Published
Jun 14, 2024
Updated
Aug 1, 2024
Vendor
Rockwell Automation
Product
CompactLogix 5480 Controllers
Classifications
CWE-670, T0814
Attack vector
adjacent
Privileges
unauthenticated

Timeline

How it unfolded

  1. Jun 14, 2024CVE publishedPublication date reported by the CVE source.
  2. Aug 1, 2024Record updatedLatest update available in the CVE record.

Exploitability

Present is not the same as exploitable

Compare your product and version with the public record. A matching version still requires validation against your environment.

Is a vulnerable build present?

Compare these published version ranges with your installed build and any vendor patches.

  1. Affected versionversion=34.011

What conditions does exploitation require?

Attack vectoradjacent
Required privilegesunauthenticated

What is affected?

Rockwell Automation · CompactLogix 5480 Controllersversion=34.011
Rockwell Automation · GuardLogix 5580 Safety Controllersversion=34.011
Rockwell Automation · 1756-EN4version=4.001
Rockwell Automation · GuardLogix 5580version=34.011
Rockwell Automation · ControlLogix 5580 Controllersversion=34.011
Rockwell Automation · Compact GuardLogix 5380version=34.011
Rockwell Automation · CompactLogix 5380 Controllersversion=34.011

Published CVSS scores

6.5NIST NVDCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
8.3Rockwell AutomationCVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H
7.4Rockwell AutomationCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

CVSS describes severity. EPSS estimates exploitation probability.

Attacks

What attackers are doing with it

Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.

Daily unique IPsNo honeypot observations are available for this CVE in the selected window.

No observations available

Sep 10, 2026Sep 16, 2026
Latest reporting daySep 16, 2026
Latest daily unique IPsUnavailable
Prior 30-day averageUnavailable
SourceShadowserver honeypots (KEV)
Vectoradjacent
Privilegesunauthenticated
Known exploitationUnconfirmed
Public exploitUnconfirmed

Weakness, pattern, technique

CWE-670Always-Incorrect Control Flow Implementation
T0814Denial of Service

Public exploit references

No public exploit references are available in this record.