CVE-2024-4009

Actuator manipulation via lost KNX sequence numbers

Published Jun 5, 2024 · Updated Mar 27, 2025

Replay protection failure in ABB KNX Secure displays and BCUs allows attackers to inject captured telegrams after bus power loss. Affected firmware does not persist KNX telegram sequence numbers across a bus power failure, so the last message is accepted when replayed with an incremented number. Access to the local KNX bus and a power interruption are required; accepted telegrams impersonate a device and can operate lights, blinds, HVAC, or doors.

CVSS severity9.2
Critical
EPSS probability0.14%
Next 30 days · Sep 16, 2026
Known exploitationUnconfirmed
Based on sourced intelligence
Hinoki checkNot available
Coverage for this vulnerability

See if you're affected

Explore vulnerability checks for your environment with Hinoki.

Book a demo

Summary

What happened

Replay protection failure in ABB KNX Secure displays and BCUs allows attackers to inject captured telegrams after bus power loss. Affected firmware does not persist KNX telegram sequence numbers across a bus power failure, so the last message is accepted when replayed with an incremented number. Access to the local KNX bus and a power interruption are required; accepted telegrams impersonate a device and can operate lights, blinds, HVAC, or doors.

The record

CVE
CVE-2024-4009
Published
Jun 5, 2024
Updated
Mar 27, 2025
Vendor
GENEREX SYSTEMS Computervertriebsgesellschaft mbH
Product
BCU KNX, BA-U1.0.21
Classifications
CWE-294, T0831
Attack vector
local
Privileges
unauthenticated

Timeline

How it unfolded

  1. Jun 5, 2024CVE publishedPublication date reported by the CVE source.
  2. Mar 27, 2025Record updatedLatest update available in the CVE record.

Exploitability

Present is not the same as exploitable

Compare your product and version with the public record. A matching version still requires validation against your environment.

Is a vulnerable build present?

Compare these published version ranges with your installed build and any vendor patches.

  1. Affected versionversion=1.3.0.33

What conditions does exploitation require?

Attack vectorlocal
Required privilegesunauthenticated

What is affected?

GENEREX SYSTEMS Computervertriebsgesellschaft mbH · BCU KNX, BA-U1.0.21version=1.3.0.33
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · BCU KNX, BA-U1.0.11version=1.3.0.33
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · RoomTouch 4, RT/U12.86.11-825version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · 2.4 Display 63, SD/U12.63.11-825version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · 2.4 Display 55, SD/U12.55.11-825version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · RoomTouch 4, RT/U12.86.1-825version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · RoomTouch 4, RT/U12.86.11-811version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · RoomTouch 4, RT-U12-86-1-811version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · BCU KNX, BA-U1.0.1version=1.3.0.33
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · 2.4 Display 70, SD/U12.70.11-4015version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · 2.4 Display 70, SD-U12-70-1-4015version=1.00
GENEREX SYSTEMS Computervertriebsgesellschaft mbH · 2.4 Display 55, SD/SD/U12.55.1-825version=1.00

Published CVSS scores

9.2ABBCVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H
7.8NIST NVDCVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
7.3ABBCVSS:4.0/AV:L/AC:L/AT:P/PR:N/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/S:N/AU:N/V:D/RE:M/U:Green
8.3ABBCVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H/E:P/RL:O/RC:C

CVSS describes severity. EPSS estimates exploitation probability.

Attacks

What attackers are doing with it

Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.

Daily unique IPsNo honeypot observations are available for this CVE in the selected window.

No observations available

Sep 10, 2026Sep 16, 2026
Latest reporting daySep 16, 2026
Latest daily unique IPsUnavailable
Prior 30-day averageUnavailable
SourceShadowserver honeypots (KEV)
Vectorlocal
Privilegesunauthenticated
Known exploitationUnconfirmed
Public exploitUnconfirmed

Weakness, pattern, technique

CWE-294Authentication Bypass by Capture-replay
T0831Manipulation of Control

Public exploit references

No public exploit references are available in this record.