CVE-2023-45321

MQTT credential interception via cleartext enrollment HTTP

Published Oct 25, 2023 · Updated Sep 11, 2024

Cleartext transmission in Bosch Rexroth ctrlX HMI WR21 before RC7 allows man-in-the-middle attackers to intercept MQTT credentials. During manual server-IP enrollment, the onboard Android Client retrieves the MQTT address, username, and password over unencrypted HTTP. Exploitation requires access to the panel's subnet and method 1 enrollment; the disclosed credentials permit authentication to the remote-management broker.

CVSS severity8.3
High
EPSS probability0.12%
Next 30 days · Sep 16, 2026
Known exploitationUnconfirmed
Based on sourced intelligence
Hinoki checkNot available
Coverage for this vulnerability

See if you're affected

Explore vulnerability checks for your environment with Hinoki.

Book a demo

Summary

What happened

Cleartext transmission in Bosch Rexroth ctrlX HMI WR21 before RC7 allows man-in-the-middle attackers to intercept MQTT credentials. During manual server-IP enrollment, the onboard Android Client retrieves the MQTT address, username, and password over unencrypted HTTP. Exploitation requires access to the panel's subnet and method 1 enrollment; the disclosed credentials permit authentication to the remote-management broker.

The record

CVE
CVE-2023-45321
Published
Oct 25, 2023
Updated
Sep 11, 2024
Vendor
Bosch Rexroth AG
Product
ctrlX HMI Web Panel WR2107
Classifications
CWE-319, T1557
Attack vector
adjacent
Privileges
unauthenticated

Timeline

How it unfolded

  1. Oct 25, 2023CVE publishedPublication date reported by the CVE source.
  2. Sep 11, 2024Record updatedLatest update available in the CVE record.

Exploitability

Present is not the same as exploitable

Compare your product and version with the public record. A matching version still requires validation against your environment.

Is a vulnerable build present?

Compare these published version ranges with your installed build and any vendor patches.

  1. Affected versionversion=0 <RC7(Build date 20231107)
  2. Affected versionversion=all

What conditions does exploitation require?

Attack vectoradjacent
Required privilegesunauthenticated

What is affected?

Bosch Rexroth AG · ctrlX HMI Web Panel WR2107version=0 <RC7(Build date 20231107); version=all
Bosch Rexroth AG · ctrlX HMI Web Panel WR2115version=all
Bosch Rexroth AG · ctrlX HMI Web Panel WR2110version=all

Published CVSS scores

8.8NIST NVDCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
8.3Robert Bosch GmbHCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L

CVSS describes severity. EPSS estimates exploitation probability.

Attacks

What attackers are doing with it

Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.

Daily unique IPsNo honeypot observations are available for this CVE in the selected window.

No observations available

Sep 10, 2026Sep 16, 2026
Latest reporting daySep 16, 2026
Latest daily unique IPsUnavailable
Prior 30-day averageUnavailable
SourceShadowserver honeypots (KEV)
Vectoradjacent
Privilegesunauthenticated
Known exploitationUnconfirmed
Public exploitUnconfirmed

Weakness, pattern, technique

CWE-319Cleartext Transmission of Sensitive Information
T1557Adversary-in-the-Middle

Public exploit references

No public exploit references are available in this record.

Labels summarize the accepted research assessment. They do not indicate a test against your environment.

Technologies

Your stack

See the directory against your own environment.

Your stack

Check the software in your environment

Book a demo to see how Hinoki identifies affected software and validates exploitability in your environment.