CVE-2022-34819Network attack vector

Remote code execution via malformed SRCS VPN messages

Published Jul 12, 2022 · Updated Apr 21, 2025

Heap overflow in Siemens SIMATIC and SIPLUS CP firmware allows remote attackers to execute code through malformed SRCS VPN messages. The enabled SRCS VPN parser insufficiently validates fields in messages received on UDP port 5243 before copying them into heap storage. The feature is disabled by default; exposure requires its use, and successful exploitation runs code in the device context.

CVSS severity10.0
Critical
EPSS probability2.02%
Next 30 days · Sep 16, 2026
Known exploitationUnconfirmed
Based on sourced intelligence
Hinoki checkNot available
Coverage for this vulnerability

See if you're affected

Explore vulnerability checks for your environment with Hinoki.

Book a demo

Summary

What happened

Heap overflow in Siemens SIMATIC and SIPLUS CP firmware allows remote attackers to execute code through malformed SRCS VPN messages. The enabled SRCS VPN parser insufficiently validates fields in messages received on UDP port 5243 before copying them into heap storage. The feature is disabled by default; exposure requires its use, and successful exploitation runs code in the device context.

The record

CVE
CVE-2022-34819
Published
Jul 12, 2022
Updated
Apr 21, 2025
Vendor
Siemens
Product
SIPLUS S7-1200 CP 1243-1 RAIL
Classifications
CWE-122, CWE-787, T0866
Attack vector
network
Privileges
unauthenticated

Timeline

How it unfolded

  1. Jul 12, 2022CVE publishedPublication date reported by the CVE source.
  2. Apr 21, 2025Record updatedLatest update available in the CVE record.

Exploitability

Present is not the same as exploitable

Compare your product and version with the public record. A matching version still requires validation against your environment.

Is a vulnerable build present?

Compare these published version ranges with your installed build and any vendor patches.

  1. Affected versionversion=All versions < V3.3.46

What conditions does exploitation require?

Attack vectornetwork
Required privilegesunauthenticated

What is affected?

Siemens · SIPLUS S7-1200 CP 1243-1 RAILversion=All versions < V3.3.46
Siemens · SIMATIC CP 1543-1version=All versions < V3.0.22
Siemens · SIMATIC CP 1243-1version=All versions < V3.3.46
Siemens · SIMATIC CP 1543SP-1version=All versions >= V2.0 < V2.2.28
Siemens · SIMATIC CP 1242-7 V2version=All versions < V3.3.46
Siemens · SIPLUS NET CP 1242-7 V2version=All versions < V3.3.46
Siemens · SIMATIC CP 1243-8 IRCversion=All versions < V3.3.46
Siemens · SIMATIC CP 1243-7 LTE USversion=All versions < V3.3.46
Siemens · SIPLUS NET CP 1543-1version=All versions < V3.0.22
Siemens · SIMATIC CP 1542SP-1 IRCversion=All versions >= V2.0 < V2.2.28
Siemens · SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAILversion=All versions >= V2.0 < V2.2.28
Siemens · SIPLUS S7-1200 CP 1243-1version=All versions < V3.3.46
Siemens · SIMATIC CP 1243-7 LTE EUversion=All versions < V3.3.46
Siemens · SIPLUS ET 200SP CP 1543SP-1 ISECversion=All versions >= V2.0 < V2.2.28
Siemens · SIPLUS ET 200SP CP 1542SP-1 IRC TX RAILversion=All versions >= V2.0 < V2.2.28

Published CVSS scores

10.0Siemens AGCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
9.3NIST NVDAV:N/AC:M/Au:N/C:C/I:C/A:C

CVSS describes severity. EPSS estimates exploitation probability.

Attacks

What attackers are doing with it

Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.

Daily unique IPsNo honeypot observations are available for this CVE in the selected window.

No observations available

Sep 10, 2026Sep 16, 2026
Latest reporting daySep 16, 2026
Latest daily unique IPsUnavailable
Prior 30-day averageUnavailable
SourceShadowserver honeypots (KEV)
Vectornetwork
Privilegesunauthenticated
Known exploitationUnconfirmed
Public exploitUnconfirmed

Weakness, pattern, technique

CWE-122Heap-based Buffer Overflow
CWE-787Out-of-bounds Write
T0866Exploitation of Remote Services

Public exploit references

No public exploit references are available in this record.