PLC service interruption via crafted port 102 packets
Published Feb 9, 2022 · Updated Apr 18, 2025
Memory exhaustion in Siemens SIMATIC industrial controllers allows remote attackers to cause a denial-of-service condition over TCP port 102. The affected firmware fails to release memory after processing specially prepared packets, exhausting PLC resources. No authentication or user interaction is required; successful exploitation interrupts PLC operation until the device is restarted.
Summary
What happened
Memory exhaustion in Siemens SIMATIC industrial controllers allows remote attackers to cause a denial-of-service condition over TCP port 102. The affected firmware fails to release memory after processing specially prepared packets, exhausting PLC resources. No authentication or user interaction is required; successful exploitation interrupts PLC operation until the device is restarted.
The record
- CVE
- CVE-2021-37205
- Published
- Feb 9, 2022
- Updated
- Apr 18, 2025
- Vendor
- Siemens
- Product
- SIMATIC S7-1500 CPU
- Classifications
- CWE-401, T0814
- Attack vector
- network
- Privileges
- unauthenticated
Timeline
How it unfolded
- Feb 9, 2022CVE publishedPublication date reported by the CVE source.
- Apr 18, 2025Record updatedLatest update available in the CVE record.
Exploitability
Present is not the same as exploitable
Compare your product and version with the public record. A matching version still requires validation against your environment.
Is a vulnerable build present?
Compare these published version ranges with your installed build and any vendor patches.
- Affected versionversion=All versions >= V2.9.2 < V2.9.4
What conditions does exploitation require?
What is affected?
Published CVSS scores
CVSS describes severity. EPSS estimates exploitation probability.
Attacks
What attackers are doing with it
Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.
Weakness, pattern, technique
Public exploit references
No public exploit references are available in this record.
Labels summarize the accepted research assessment. They do not indicate a test against your environment.
Technologies
Your stack
See the directory against your own environment.
Your stack
Check the software in your environment
Book a demo to see how Hinoki identifies affected software and validates exploitability in your environment.
Book a demo