Unauthenticated program download via password validation failure
Published Aug 10, 2021 · Updated Aug 4, 2024
Improper authentication in Siemens SIMATIC S7-1200 V4.5.0 allows remote attackers to download arbitrary PLC programs over the network. A CPU provisioned with TIA Portal V13 fails to validate configured access-level passwords when later contacted through TIA Portal, so it accepts a program download without the required credential. The flaw is limited to firmware V4.5.0 provisioned with the original V13 release; V13 SP1 or later provisioning does not create the vulnerable state.
Summary
What happened
Improper authentication in Siemens SIMATIC S7-1200 V4.5.0 allows remote attackers to download arbitrary PLC programs over the network. A CPU provisioned with TIA Portal V13 fails to validate configured access-level passwords when later contacted through TIA Portal, so it accepts a program download without the required credential. The flaw is limited to firmware V4.5.0 provisioned with the original V13 release; V13 SP1 or later provisioning does not create the vulnerable state.
The record
- CVE
- CVE-2021-37172
- Published
- Aug 10, 2021
- Updated
- Aug 4, 2024
- Vendor
- Siemens
- Product
- SIMATIC S7-1200
- Classifications
- CWE-287, T0889
- Attack vector
- network
- Privileges
- unauthenticated
Timeline
How it unfolded
- Aug 10, 2021CVE publishedPublication date reported by the CVE source.
- Aug 4, 2024Record updatedLatest update available in the CVE record.
Exploitability
Present is not the same as exploitable
Compare your product and version with the public record. A matching version still requires validation against your environment.
Is a vulnerable build present?
Compare these published version ranges with your installed build and any vendor patches.
- Affected versionversion=V4.5.0
What conditions does exploitation require?
What is affected?
Attacks
What attackers are doing with it
Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.
Public exploit references
No public exploit references are available in this record.
Labels summarize the accepted research assessment. They do not indicate a test against your environment.