Remote-access enablement via unauthenticated C-Gate service
Published Jul 21, 2021 · Updated Aug 3, 2024
Missing authentication in Schneider Electric C-Bus Toolkit 1.15.8 and earlier allows remote attackers to enable remote access via a webpage. The C-Gate 2 Service listens on TCP port 20023 and permits a crafted webpage to enable remote access without authenticating the request. Exploitation requires the target to visit the malicious page or open a malicious file; the resulting access can be chained with other flaws to execute code as SYSTEM.
Summary
What happened
Missing authentication in Schneider Electric C-Bus Toolkit 1.15.8 and earlier allows remote attackers to enable remote access via a webpage. The C-Gate 2 Service listens on TCP port 20023 and permits a crafted webpage to enable remote access without authenticating the request. Exploitation requires the target to visit the malicious page or open a malicious file; the resulting access can be chained with other flaws to execute code as SYSTEM.
The record
- CVE
- CVE-2021-22784
- Published
- Jul 21, 2021
- Updated
- Aug 3, 2024
- Vendor
- Schneider Electric
- Product
- C-Bus Toolkit
- Classifications
- CWE-306, T1189
- Attack vector
- network
- Privileges
- unauthenticated
Timeline
How it unfolded
- Jul 21, 2021CVE publishedPublication date reported by the CVE source.
- Aug 3, 2024Record updatedLatest update available in the CVE record.
Exploitability
Present is not the same as exploitable
Compare your product and version with the public record. A matching version still requires validation against your environment.
Is a vulnerable build present?
Compare these published version ranges with your installed build and any vendor patches.
- Affected versionversion=C-Bus Toolkit v1.15.8 and prior
What conditions does exploitation require?
What is affected?
Published CVSS scores
CVSS describes severity. EPSS estimates exploitation probability.
Attacks
What attackers are doing with it
Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.
Weakness, pattern, technique
Public exploit references
No public exploit references are available in this record.