Service interruption via unauthenticated Modbus reboot command
Published Feb 4, 2022 · Updated Apr 15, 2025
Improper access control in SeaConnect 370W 1.3.34 allows remote attackers to reboot the device through an unauthenticated Modbus request. DispatchModbusRequest routes proprietary function code 0x13 directly to the Reboot routine without authenticating the sender. Modbus TCP must be enabled, after which repeated requests on TCP port 502 can keep the edge module unavailable.
Summary
What happened
Improper access control in SeaConnect 370W 1.3.34 allows remote attackers to reboot the device through an unauthenticated Modbus request. DispatchModbusRequest routes proprietary function code 0x13 directly to the Reboot routine without authenticating the sender. Modbus TCP must be enabled, after which repeated requests on TCP port 502 can keep the edge module unavailable.
The record
- CVE
- CVE-2021-21964
- Published
- Feb 4, 2022
- Updated
- Apr 15, 2025
- Vendor
- Sealevel Systems, Inc.
- Product
- SeaConnect 370W
- Classifications
- CWE-306, CWE-284, T1529
- Attack vector
- network
- Privileges
- unauthenticated
Timeline
How it unfolded
- Feb 4, 2022CVE publishedPublication date reported by the CVE source.
- Apr 15, 2025Record updatedLatest update available in the CVE record.
Exploitability
Present is not the same as exploitable
Compare your product and version with the public record. A matching version still requires validation against your environment.
Is a vulnerable build present?
Compare these published version ranges with your installed build and any vendor patches.
- Affected versionversion=Sealevel Systems, Inc. SeaConnect 370W v1.3.34
What conditions does exploitation require?
What is affected?
Published CVSS scores
CVSS describes severity. EPSS estimates exploitation probability.
Attacks
What attackers are doing with it
Daily unique IPs observed by Shadowserver honeypots for known exploited vulnerabilities (KEVs). Missing observations do not establish an absence of attacks.
Weakness, pattern, technique
Public exploit references
- Cisco Talos Modbus reboot proof of conceptproof of concept · demonstrated